| 1 pce three-phase oil filled rectifier transformer arrangement | 
                    
                                                  | designed for outdoor installation and includes two rectifier transformers | 
                    
                                                  | in double tier design and two interphase transformers as well | 
                    
                                                  | as the OFAF cooling equipment, protection and monitoring auxiliaries. | 
                    
                                                  |  | 
                    
                                                  | The primary of the one tier of the rectifier transformer is | 
                    
                                                  | arranged in star connection, the primary side of the other tier | 
                    
                                                  | in delta connection. This way the transformer combinations has a | 
                    
                                                  | 12-pulse phase effect. The connection is therefore Ya0 + Yy0y6 + Dy5y11. |