| GENERATOR STEP-UP TRANSFORMER WITH DUAL PRIMARY VOLTAGE (EU ECO DESIGN) | 
                    
                                                  |  | 
                    
                                 
                  | Quantity | : 1 pce | 
                    
                                 
                  | Brand | : BTB Trafo | 
                    
                                 
                  | Year of Manufacture | : 2018 | 
                    
                                 
                  | Basic Transformer Design | : Cast Resin | 
                    
                                 
                  | Ingress Protection | : IP34 | 
                    
                                 
                  | Classifications | : E2 - C2 - F1 | 
                    
                                 
                  | Application | : Generator Step-up Transformer | 
                    
                                 
                  | Number of Phases | : Three-phase | 
                    
                                 
                  | Rated Power | : 2500/3150 kVA | 
                    
                                 
                  | Cooling | : AN/AF-Cooling | 
                    
                                 
                  | Voltage Ratio | : 21000 (10500) / 6000 V | 
                    
                                 
                  | Prim .Ins. Level  (Um/LI/AC) | : 24 kV / LI 125 / AC 50 | 
                    
                                 
                  | Sec. Ins. Level  (Um/LI/AC) | : 7,2 kV / LI 60 / AC 20 | 
                    
                                 
                  | Voltage Regulation | : off-circuit, bolted links | 
                    
                                 
                  | Tapping Range | : see table below | 
                    
                                 
                  | Temperature Class (HV/LV) | : Class F / Class F | 
                    
                                 
                  | Frequency | : 50 Hz | 
                    
                                 
                  | Vector Group | : YNd11 | 
                    
                                 
                  | Standards | : IEC 60076-11 | 
                    
                                 
                  | Impedance | : 6,07 % | 
                    
                                 
                  | No-Load Losses | : 3 632 W (fulfils EU Eco Design Directive) | 
                    
                                 
                  | Load Losses | : 16 518 W @21Kv (fulfils EU Eco Design Directive) | 
                    
                                 
                  | Outer Dimensions (LxWxH) | : 2700x1600x2842 mm | 
                    
                                 
                  | Total Weight (IP34) | : ~6780 kg | 
                    
                                                  |  | 
                    
                                 
                  | Tapping Range - Primary 1 | : 22 050 V | 
                    
                                 
                  |  | : 21 525 V | 
                    
                                 
                  |  | : 21 000 V | 
                    
                                 
                  |  | : 20 475 V | 
                    
                                 
                  |  | : 19 950 V | 
                    
                                                  |  | 
                    
                                 
                  | Tapping Range - Primary 2 | : 11 025 V | 
                    
                                 
                  |  | : 10 763 V | 
                    
                                 
                  |  | : 10 500 V | 
                    
                                 
                  |  | : 10 238 V | 
                    
                                 
                  |  | : 9 975 V |